Specification of Cable Gland Hawke Explosion Proof 501/453/RAC
Application
Outdoor or indoor use.
For use with single wire armour ‘W’, wire braid ‘X’ and steel tape armour ‘Z’ elastomer and plastic insulated cables.
Features
Provides armour clamping using one clamping arrangement for all armour/braid types.
Provides a seal on the cables inner sheath.
Deluge protection option available, contact Hawke Technical Sales for details.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.
Materials & Finishes
The 501/453/RAC cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.
Technical Data
- Exdb IIC Gb, Exeb IIC Gb, Extb IIIC Db
- Certificate No's
- Baseefa06ATEX0056X and IECEx BAS 06.0013X.
- Suitable for use in:
- Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
- Construction and Test Standards:
- IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7 and IEC/EN 60079-31.
- Ingress Protection:
- IP66, IP67 and IP 68* (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
- *Additional installation procedures required.
- Deluge Protection to:
- DTS01 (Deluge seal optional).
- Operating Temperature Range:
- -60°C to +100°C
- Assembly Instruction Sheet:
- AI 302.
Cable Gland